02D Input Amps – This menu displays the total AC amps being used
by the inverter for charging and any connected load at the output of
the inverter. This reading is always displayed as a positive (+) number.
Example: If the charger is using 20A from the AC source and the load
connected to the inverter output is using 10A, the combined load on
the incoming AC source is 30A. So, 30A is displayed as the input amps.
02E Inv/Chg Amps – This menu displays the inverter or charger amps.
A negative (–) amps reading indicates the inverter is powering the in-
verter loads and the batteries are discharging (inverter amps). A positive
(+) amps reading indicates the inverter is using the AC input source to
charge the batteries (charger amps).
02F Input AC1 – This menu displays the RMS value of the AC voltage
at the inverter's AC1/HOT IN 1 and NEUTRAL terminals.
02G Input AC2 – This menu displays the RMS value of the AC input
voltage applied to the inverter's AC2 and NEUTRAL terminals.
Info: The 02G Input AC2 menu only displays if the remote is con-
nected to a dual source inverter/charger that has an AC1 and AC2
input such as the MSH4024E.
Info: If the 02G Input AC2 menu displays voltage (~ 50 volts),
but the generator is off or nothing is connected to the AC2 input,
the AC2 neutral-to-ground bond connection is not correct or con-
nected.

METER: 03 AGS Meters

Refer to Section 7.0 for detailed information on the AGS menus that are
available from the ME-ARC remote's METER button.

METER: 04 BMK Meters

Refer to Section 8.0 for detailed information on the BMK menus that are
available from the ME-ARC remote's METER button.

3.3.4 SETUP Button and Menus

Pressing the SETUP button provides access to the menu items and settings
that enable you to confi gure the ME-ARC display, inverter/charger, ME-AGS-N,
and the ME-BMK. Review each menu item to determine if you need to adjust
any settings to meet your system requirements.
Info: The fi rst screen that may appear when the SETUP button is
pushed is a password screen. If the PIN has been set under the TECH
button's 05 SETUP PIN menu item, the fi rst screen is the Setup PIN
menu. The proper PIN must now be entered in order to access the
SETUP menus. After fi ve minutes from the last button push, the
display automatically returns to the remote home screen and the
PIN must be reentered in order to access the SETUP menus. Refer
to the TECH menu's 05 SETUP PIN menu item to set or change the
PIN number.
Info: In any SETUP menu that contains a range of settings, if the fi rst
and last settings are equal (set to the same value) the function will
be disabled, even if selected/enabled from the CTRL menu.