7.4 Enabling the ME-AGS-N

Before the AGS can begin operating/monitoring for an autostart condition (us-
ing active AGS settings in your ME-ARC remote control), it must be enabled.
To enable the AGS:
1.
Press the CTRL button on the ME-ARC remote, and then rotate the SELECT
knob to the 03 Gen Control menu.
2.
Press the SELECT knob. The Set Gen Control screen displays with the
current gen control setting and an arrow to the right.
3.
Turn the SELECT knob to the AUTO setting.
4.
Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen.
The AGS is now ready to automatically start/stop the generator once an
autostart condition is satisfi ed.
Note: If power is lost to your remote, the AGS control setting will return to the
default OFF setting. Once power is restored, you must enable the AGS again.

7.5 Starting and Stopping the Generator

The generator can be manually started/stopped, as well as autostarted/au-
tostopped using the available settings from your ME-ARC.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the follow-
ing autostart/autostop conditions must be pre-set (see Section 7.1):
Autostart Conditions
04A Gen Run VDC (pp. 66-68)
04B Gen Run Time (p. 68)
04C Gen Run Amps (pp. 68-69)
04D Gen Run SOC (pp. 69-70)
04E Gen Run Temp (pp. 70-71)
04G Quiet Time (pp. 72-74)
04H Gen Run Exercise (pp. 74-75)
To manually start the generator:
1.
Press the CTRL button.
2.
Turn the SELECT knob to the 03 Gen Control menu.
3.
Press the SELECT knob. The Set Gen Control menu displays with an arrow
to the right of the current setting.
4.
Turn the SELECT knob to the ON setting.
5.
Press the SELECT knob again to select this setting. The selection arrow
appears to the right of the screen. The generator should start at this time.
If the generator does not start as expected, refer to Section 7.8 "ME-AGS-N
Remote Troubleshooting" in this manual.
© 2012 Magnum Energy, Inc.
7.0 Using an AGS Module
Autostop Conditions
04A Gen Run VDC (pp. 66-68)
04B Gen Run Time (p. 68)
04C Gen Run Amps (pp. 68-69)
04D Gen Run SOC (pp. 69-70)
04E Gen Run Temp (pp. 70-71)
04F Max Gen Run Time (p. 72)
04G Quiet Time (pp. 72-74)
04H Gen Run Exercise (pp. 74-75)