Auxiliary Outputs Check; Sounder Circuits Check; Fault Relay Wiring - Honeywell NOTIFIER ID2000 Series Installation & Commissioning Manual

Hide thumbs Also See for NOTIFIER ID2000 Series:
Table of Contents

Advertisement

ID2000 Series Installation & Commissioning Manual
+ve
-ve
88.888
Ohms
Volts
-ve
+ve
NO
C
NC
NO
FAULT RELAY IN
FAULT RELAY IN
NON-ENERGISED
ENERGISED STATE,
STATE, PANEL IN FAULT
PANEL QUIESCENT
8.4.5 24V Auxiliary Outputs Check
There are two monitored 24V Auxiliary Outputs. Before
connecting any circuit to either of these outputs check that:
a. The external wiring is not short circuit.
b. There are no forward-biased diodes (as used for
example with end-of line power monitoring relays)
connected across the external wiring.
When connecting to the output, observe correct
polarity!

8.4.6 Sounder Circuits Check

Before the sounder circuits are connected it is
recommended that all detection circuits have been
checked and that there is no possibility of spurious alarm
conditions being generated. The sounders should be
polarized and suppressed using IN4002 (or similar)
diodes and the circuits should be fitted with 4k7 end-of-
line resistors. Perform the following checks:
1 Use a low-voltage multimeter to check the resistance
across each of the sounder circuits:
4k7
i.
ii. With the multimeter connected to the circuit in normal
2 If electronic sounders are used this test will not reveal
reversed devices. It is, therefore, recommended that
if the circuit resistance appears correct, the following
be done:
i
ii
iii Using a multimeter, measure the voltage across
3 When the sounder circuits have been connected, the
sounders may be tested using the 'EVACUATE'
button.

8.4.7 Fault Relay Wiring

The markings for the Fault Relay connector SK8 on the
Base Board refer to the non-energised state of the relay.
This is the fault condition. In the panel's quiescent state,
the relay is energised. These states are shown in the
illustration opposite.
C
NC
45
With the meter connected in reverse polarity (+ve
to '-ve' and -ve to '+ve') the reading should be 4k7.
polarity (+ve to '+ve' and -ve to '-ve') the meter may
indicate a lower value. This is because of the forward-
biased diodes in series with the sounders.
Remove the 4k7 resistors from the panel outputs.
Connect the circuit to the panel output while
observing correct polarity.
each sounder output circuit (as shown at left).
The normal voltage reading should be between
5V and 8V. If any devices are reversed, a reading
of between 1V and 2V will be indicated.
997-433-000-5, Issue 5
May 2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id2002

Table of Contents