General; Date-Dependent Functions; Installation: Sections - Honeywell NOTIFIER ID2000 Series Installation & Commissioning Manual

Hide thumbs Also See for NOTIFIER ID2000 Series:
Table of Contents

Advertisement

Only fit the electronics
module after all the other
trades have completed
their tasks!
997-433-000-5, Issue 5
May 2010
ID2000 Series Installation & Commissioning Manual

1.4 General

The ID2000 Series of intelligent fire alarm controllers are
designed for use with NOTIFIER's range of addressable
analogue sensors, control and monitoring modules and
addressable call points. A unique signalling protocol is used,
having digital address and control signals, and analogue
pulse width monitoring for the reply data from devices. The
ID2000 Series supports the use of OPAL protocol devices,
but can only poll these devices in CLIP protocol mode.
The ID2000 Series control panel design complies with the
requirements of EN54 Part 2 and Part 4.
The design of the ID2000 Series of fire control panels is
based on a modular build concept which offers the user
completely flexible system solutions. Each control panel
comprises a number of separate build modules to simplify
the installation process. The electronic components are
contained in an easy-to-fit module called the main chassis.
The control panel can be used with either an internal or
external Power Supply Unit (PSU).
The ID2000 Series fire control panels are available either as:
a. Multi-loop, user-configurable Basic Equipment Kits
b. Factory-configured, ID2002 2-loop control panels.
Any references in these manuals to configurations with
more than two loops are not applicable to the ID2002
control panel.
Each control panel has space provision for two sealed, lead-
acid batteries.
The serial communications interface operates under
RS485 protocol and enables networking of control panels
and the connection between control panels and repeaters.
While every effort is made to ensure the accuracy of the
content of this manual, the manufacturer reserves the
right to change the information without notice.
Installation
The ID2000 Series modules are easy to install providing
the recommended procedures described in this manual
are followed. To avoid inadvertant contamination of the
main chassis, comprising the PCBs and PSU, if mounted
internally, the manufacturer recommends that these items
are installed in the back box only after all other trades have
completed their tasks.

1.5 Date-dependent Functions

It should be noted that the calendar end date for this
product is 31/12/2099 (two thousand and ninety nine) and
it will perform correctly up to this date.
The calendar function has not been tested beyond this
date.