Megger Baker AWA-IV User Manual page 122

Static motor analyzer
Hide thumbs Also See for Baker AWA-IV:
Table of Contents

Advertisement

Test Procedures
23. In the Tests tab, click on Save to ensure that your new settings are retained.
24. Uncheck the Edit Test ID box if it is still highlighted (red).
25. You are now ready to test additional coils using the test reference acquired.
26. To continue testing additional coils, disconnect the coil used to acquire the reference and set it aside.
CAUTION: Ensure that the Leads Energized light turns off before removing leads from the coil.
27. Connect the next coil to be tested to the high-voltage test cables as described in the table below.
Table 5: AWA-IV high-voltage test lead connections to device under test for single-coil Surge testing.
Test Lead 1
Coil lead 1
28. Click on the Run Auto Test button and follow the prompts provided by the tester for executing the tests.
29. Both leads will be tested and the Surge Test window will close automatically. The test data is automatically saved
for each test.
30. Disconnect the coil from the tester.
31. If you need to test another coil, connect it to the tester as described above and repeat the process starting from
step 27.
110
Baker AWA-IV 71-015 EN V16 User Guide
Test Lead 2
Coil lead 2
Fig 120: Testing coils using the test reference.
Test Lead 3
Not Connected
Ground Lead
Not Connected
www.megger.com

Advertisement

Table of Contents
loading