NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Table 3-15 DIP switches of the T/H sensor
Position
Return air
Cold aisle
Hot aisle
----End

3.12 Verification After Installation

Table
Record results in the table after verification.
Table 3-16 Check items on the cabinet installation
Check Item
Cabinet
Issue 03 (2020-01-10)
Name
Return air
T/H 1
Cold aisle
T/H 1
Cold aisle
T/H 2
Cold aisle
T/H 3
Hot aisle
T/H 1
Hot aisle
T/H 2
Hot aisle
T/H 3
By default, the address of an T/H sensor provided by Huawei is 1.
No DIP switch operation is required for the last RS485_R port.
After setting communications addresses for T/H sensors, choose Settings > System Settings > T/H
Sensor from the main menu and enable the T/H sensor in the aisle. Otherwise, the sensor does not
work.
3-16,
Table 3-17
and
Table 3-18
Expected Result
The cabinet is installed properly, without
any tilt.
The cabinet is secured to the base using
bolts.
The foreign matter inside the cabinet such
as cable ties and stubs is cleaned up.
Copyright © Huawei Technologies Co., Ltd.
Address
DIP Switch Sequence
1
2
1
ON
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
21
ON
OFF
22
OFF
ON
23
ON
ON
list the items for the verification after installation.
3 Installation Guide
3
4
5
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
85