NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
For a smart cooling product with heating and humidification functions in the active route,
the general circuit breaker is a 63 A, feature D circuit breaker.
For a smart cooling product without heating and humidification functions or in the standby
route, the general circuit breaker is a 40 A, feature D circuit breaker.
Table 2-7 Universal parameters
Item
Power supply mode
Cooling mode
Refrigerant
Air supply mode
Maximum current
(indoor unit current +
outdoor unit current)
Power supply
Heating function
Humidification function
Pipe routing mode
Condensate pump
Water pump lift
Dimensions (H x W x
D)
Net weight
Certification
In the preceding table, No indicates that the corresponding model does not provide the
function.
Issue 03 (2020-01-10)
NetCol5000-A021HN12
D20020E1
Dual-route power supply
Air cooled
R410A
Horizontal flow
28 A
The rated mains input voltage must be three-phase, five-wire (3
Ph+N+PE), 208 V AC (187 V to 229 V) in line voltage, and
60± 3 Hz in frequency. If the front-end voltage fluctuation
exceeds this range, you are advised to add a voltage regulator.
Otherwise, the smart cooling product may generate alarms
frequently and fail to work properly.
No
No
Overhead and bottom
Yes
4 m
2000 mm x 300 mm x 1100 mm (cabinet dimensions)
2000 mm x 300 mm x 1200 mm (with an enclosure frame)
260 kg
REACH, RoHS
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
NetCol5000-A021HN12D2E12
0E1
Dual-route power supply
48 A
Yes
Yes
22