Optional) Replacing The Liquid Level Detector - Huawei NetCol5000-A021 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A021:
Table of Contents

Advertisement

NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Figure 6-21 Removing a module
Step 4 Take out the handle and pull out the module from the subrack, as shown by (2) in
When installing a new module, ensure that the handle is in the upper part of the module, and
the HUAWEI logo is in the lower left corner of the module.
Step 5 Insert the spare module into the corresponding slot, and flip the clip upwards to lock the
module.
Step 6 Install the air filter and close the rear door.
----End

6.5.12 (Optional) Replacing the Liquid Level Detector

Prerequisites
Context
Components and working principle: A liquid level detector is composed of the conductor
outer jacket, liquid level detector, switch, and card pole. A liquid level detector rises or drops
as the liquid level changes due to the magnetism of the liquid level switch, causing the reed
switch chip in the specified position inside the sensor detection pipe to move and send the
contact on/off conversion signal to control the liquid level detector.
The liquid level detector can be maintained only from the front.
Issue 03 (2020-01-10)
The liquid level detector needs to be replaced.
A spare liquid level detector of the same model is available and functional.
Tool: Phillips screwdriver
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Figure
6-21.
208