Figure 3-52 Network diagram
For CAN networking, set the DIP switch on the main control module by following the
instructions in
If Restore factory settings? The system will operate with existing settings 30s later. is
displayed when the main control module is powered on, click No and flip toggle switch 4
on the main control module to OFF (default status).
Table 3-14 Instructions about operating the DIP switch on the main control module
Toggle
Switch
1
2
3
4
Step 2 When the EMS monitors smart cooling products over RS485, the time needed for collecting
all data from a single smart cooling product is 3 seconds. In the teamwork mode of cascading
using an RS485 bus for monitoring, it takes the host 3 x N seconds to collect data from N
smart cooling products in the group. If the EMS needs more time to collect data from all
smart cooling products than what the EMS performance requires, the smart cooling products
can be grouped for data collection. Assuming that the EMS needs to collect the data from all
smart cooling products within 12 seconds, you are advised to incorporate four smart cooling
products in one group and connect the COM port shown by (7) in
smart cooling product for each group to an RS485 port on the EMS.
32 teamworked smart cooling products, four in each group, connect to the EMS.
Issue 03 (2020-01-10)
Table
3-14.
Default
Value
Site Operations
OFF
Non-teamwork control: remaining OFF
Teamwork control: Flip toggle switch 1 of the first and
last smart cooling products in the network to ON, and
toggle switch 1 of the other smart cooling products to
OFF.
ON
Monitoring branch switch. If you need to enable the
monitoring of northbound devices by group, flip toggle
ON
switches 2 and 3 to OFF. For details about how to set, see
Figure
OFF
This toggle switch determines whether to restore factory
defaults. Retain the default value (OFF) of this switch.