Connecting The Outdoor Unit On/Off Signal Cable - Huawei NetCol5000-A021 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A021:
Table of Contents

Advertisement

NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Figure 3-48 Routes of the outdoor unit on/off signal cable (RS485) and water sensor signal cable

3.11.4.2 Connecting the Outdoor Unit On/Off Signal Cable

Context
The outdoor unit signal cable can connect to a dry contact or an RS485 port (by default).
Outdoor fan control mode is set to Communicate by default. If the signal cable connects to
a dry contact, choose Settings > System Settings > Outdoor Fan > Outdoor fan control
mode, and set Outdoor fan control mode to Dry contact.
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
77

Advertisement

Table of Contents
loading

Table of Contents