NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
----End
Issue 03 (2020-01-10)
Figure 4-32 Screen displayed when the calibration is complete
Calibrating the screen by DIP switch.
a.
Flip toggle switch 1 for the LCD to ON, and others to the opposite position, and
wait for 3 seconds before calibrating.
en-us_concept_0155486444.xml#EN-US_CONCEPT_0155486444/EN-US_CONC
EPT_0155486444_mMcCpPsS_fig_02Figure 2-4
screen.
b.
Flip the fourth toggle switch to ON and others remain unchanged, and the screen
calibration function is triggered.
After 15 seconds, a dialog box indicating Are you sure you want to calibrate the
screen? If you do not click Yes or No, calibration will start automatically 10
seconds later. is displayed, as shown in
Figure 4-33 Confirming to calibrate the screen
c.
Wait for 10 seconds or tap Yes.
Figure 4-32
is displayed, the adjustment is complete.
d.
Flip toggle switch 4 for the LCD to non ON.
After the DIP switch is calibrated, flip toggle switch 1 to ON, and others to the opposite position.
You need to manually operate the operation again from the first step to trigger the touchscreen
calibration function after the calibration failure.
Copyright © Huawei Technologies Co., Ltd.
shows the toggle switches for the
Figure
4-33.
Figure 4-31
is displayed. Tap the screen. When
4 ACC Introduction
119