Huawei NetCol5000-A021 User Manual page 102

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A021:
Table of Contents

Advertisement

NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
You are not recommended to modify the parameters not listed in
Table 4-2 Parameter description
Parameter
T/H control type
Temp control
mode
Supply-air temp
set point,
Supply-air humid
set point
Return-air temp
set point,
Return-air humid
set point
Cold-aisle temp
set point,
Cold-aisle humid
set point
Issue 03 (2020-01-10)
Description
Sets Cold-aisle,
Hot-aisle,
Return-air, or
Supply-air as
required. The
temperature and
humidity set points
correspond to the
selected control type
can be set.
Controls the
temperature inside the
room or aisles based
on the Average,
Maximum, or
Minimum of the
temperatures collected
by each sensor.
Sets the required
humidity and
temperature in a room
or aisle.
Copyright © Huawei Technologies Co., Ltd.
Table
4-2.
Configuration Principle
Return-air: For a hot aisle, select
Return-air to control the temperature and
humidity around the air return vent of the
smart cooling product.
Supply-air: For a cold aisle, select
Supply-air to control the temperature and
humidity around the air supply vent of the
smart cooling product.
Cold-aisle: For a cold aisle, select
Cold-aisle to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Hot-aisle: For a hot aisle, choose
Hot-aisle to control the temperature and
humidity of the aisle. The temperature and
humidity values come from the humidity
and temperature sensor in the aisle.
Average: Select Average if the
temperature is to be controlled based on
the averaged data value collected by the
collector.
Maximum: Select Maximum if the
temperature is to be controlled based on
the maximum data value collected by the
collector.
Minimum: Select Minimum if the
temperature is to be controlled based on
the minimum data value collected by the
collector.
The ACC controls the temperature and
humidity based on the set value. For example,
if Temp control type is set to Return-air,
Return-air temp set point is set to 30.0, and
Return-air humid set point is set to 25.0, the
ACC will control the temperature and
humidity around the return-air vent of the
smart cooling product to a temperature of
30° C and humidity of 25% RH.
4 ACC Introduction
94