3.11.2 Connecting the Indoor Unit Power Cable

Prerequisites
Before connecting cables, remove the top cover from the power terminals.
Context
Keep cables away from the compressor, fan, and copper pipe (if unavoidable, take protective
measures), and connect cables securely.
Procedure
Step 1 For single power supply, connect the external power cable to the L1, L2, L3, and N ports of
the AC1 terminal. For dual power supply, connect the external power cable to the L1, L2, L3,
and N ports of the AC1 and AC2 terminals. See
Step 2 Connect the PE cable to the cabinet ground bar, as shown in
Ensure that there is no reverse or open phase for the input power cable of the smart cooling
product.
Issue 03 (2020-01-10)
Route power cables from the top or bottom.
For the switch and cable specifications, see
The cables should be routed in from the cable clip.
Copyright © Huawei Technologies Co., Ltd.