Huawei NetCol5000-A021 User Manual page 108

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A021:
Table of Contents

Advertisement

NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Parameter
Cascade
Large ring
cooling
capacity P
Large ring
cooling
capacity I
Large ring
cooling
capacity D
Cooling
capacity
adjustment
period
L1/L2
linkage
cooling stop
Issue 03 (2020-01-10)
Description
humidity control type
and set points of the
master device and
other parameters) to
the slave device, and
all the smart cooling
products in the group
refer to the mode
delivered by the
master device.
When the requirement
control is Disable, the
master device does
not synchronize data
to the slave device,
and all the smart
cooling products
operate based on their
own requirements,
not referring to the
mode delivered by the
master device.
After the requirement
control is enabled, you
can configure Cascade.
The cascade function
starts standby smart
cooling products if the
active one cannot meet
the refrigerating
requirements.
Proportion coefficient in
L1/L2 linkage PID
control.
Integration coefficient in
L1/L2 linkage PID
control.
Differential coefficient in
L1/L2 linkage PID
control.
Adjustment period in
L1/L2 linkage PID
control.
Reference temperature at
which the smart cooling
product stops cooling in
the cooling mode in
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
If the heat load to the
device increases, the
cascade function is
recommended.
You are not
recommended to change
the value.
You are not
recommended to change
the value.
You are not
recommended to change
the value.
You are not
recommended to change
the value.
Set this parameter based
on the lowest
temperature allowed
onsite. Normally you are
4 ACC Introduction
Default Value
Disable
0.10
350s
10s
5s
18.0° C
100