NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Alarm
Alarm Name
ID
a167
Secondary
power 24 V
overvoltage
a168
Secondary
power 24 V
undervoltage
a169
Power phase A
open
a170
Power phase B
open
a171
Power phase C
open
a172
SPD 3-phase
test board
comm fault
a173
SPD 3-phase
test board
ground fault
a174
SPD failed
a175
L1/L2 linkage
humidity not
met
Issue 03 (2020-01-10)
Alarm
Impact
Severity
Major
The alarm is
generated.
Major
The alarm is
generated.
Critical
The alarm is
generated, and
the system
shuts down.
Critical
The alarm is
generated, and
the system
shuts down.
Critical
The alarm is
generated, and
the system
shuts down.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated, and
the L1/L2
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
Solution
The secondary
Replace the secondary power
power supply is
supply module.
faulty.
The secondary
Replace the secondary power
power supply is
supply module.
faulty.
1. The power grid
1. Check the power grid.
is unstable.
2. Check the phase A cable is
2. The phase A
cable is faulty.
1. The power grid
1. Check the power grid.
is unstable.
2. Check the phase B cable is
2. The phase B
cable is faulty.
1. The power grid
1. Check the power grid.
is unstable.
2. Check the phase C cable is
2. The phase C
cable is faulty.
1. The
1. Check the communications
communication
s cable is not
2. Replace the SPD
properly
connected.
3. Maintain or replace the
2. The SPD
three-phase test
board is faulty.
3. The
communication
port of the
control board is
faulty.
1. The SPD
1. Check the SPD three-phase
three-phase test
board ground
2. Replace the SPD
cable is not
properly
connected.
2. The SPD
three-phase test
board is faulty.
The SPD
Replace the SPD three-phase
three-phase test
test board.
board is faulty.
1. T/H sensor of
1. Maintain or replace the
cabinet is
faulty.
2. Maintain or replace the
faulty.
faulty.
faulty.
cable.
three-phase test board.
control board.
test board ground cable.
three-phase test board.
T/H sensor of cabinet.