NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Alarm
Alarm Name
ID
HT lock
a015
Comp exceed
runtime
a018
Indoor fan
1/2/3/4/5/6
exceed runtime
a023
Elec heater 1
HT
a024
Elec heater 1
exceed runtime
a025
Air filter
blocked
a026
Air filter exceed
runtime
Issue 03 (2020-01-10)
Alarm
Impact
Severity
the compressor
is forcibly shut
down.
Warning
The alarm is
generated.
Warning
The alarm is
generated.
Major
The alarm is
generated, and
the electric
heater is
forcibly shut
down.
Warning
The alarm is
generated.
Warning
The alarm is
generated, and
the electric
heater and
humidifier are
shut down.
Warning
The alarm is
generated.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
Solution
alarm.
alarm is generated
frequently.
NOTE
The accumulated
Maintain or replace the comp
runtime of the
and clear the accumulated
comp exceeds the
runtime.
alarm threshold.
The accumulated
Maintain or replace the indoor
runtime of the fan
fan and clear the accumulated
exceeds the alarm
runtime.
threshold.
1. The cables to
1. Check the cables to the
the temp switch
of the elec
heater are loose
2. Replace the elec heater.
or damaged.
3. Maintain or replace the
2. The temp
switch is faulty.
3. The indoor fans
are faulty.
The accumulated
Maintain or replace the elec
runtime of the elec
heater and clear the
heater exceeds the
accumulated runtime.
alarm threshold.
1. Air filters are
1. Maintain or replace the air
blocked.
2. The differential
2. Replace the differential
press switch is
faulty.
3. Adjust the threshold of the
3. The differential
press switch is
4. Maintain or replace the
set
inappropriately.
5. Check the cables to the
4. The pressure
inlet tube of the
NOTE
differential
pressure switch
is blocked or
disconnected.
5. The cables to
the differential
press switch are
loose or
damaged.
The accumulated
Maintain or replace the air
runtime of air filter
filter and clear the
After the alarm is rectified, click
Manual clear on the alarm page.
temp switch of the elec
heater.
indoor fans.
filters.
press switch.
differential press switch.
press tube.
differential press switch.
After the alarm is rectified, click
Manual clear on the alarm page.