NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Be careful when configuring alarms. Only professional maintenance personnel can change
alarm settings.
Procedure
Step 1 Choose Settings > Alarm Settings > T/H Sensor on the home screen.
displayed.
Figure 4-11 Setting alarm parameter 1
Step 2 Tap Delay following Supply-air HT.
Step 3 Set the value to 5 and tap
Issue 03 (2020-01-10)
Allow
Alarms are reported to the EMS. Active alarms are displayed on the LCD and the
system performs related protection actions.
Block
New alarms are not reported to the EMS. The EMS can detect alarms that are
generated before the blocking. Active alarms are displayed on the LCD and the
system performs related protection actions.
Disallow
Alarms are not generated and no protection actions are performed.
The method for setting each alarm is the same. This section describes how to set Delay
of Supply-air HT to 5.