Huawei NetCol5000-A021 User Manual page 163

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A021:
Table of Contents

Advertisement

NetCol5000-A021 In-row Air Cooled Smart Cooling
Product
User Manual (208 V)
Alarm
Alarm Name
ID
a035
Power
underfreq
a037
Power phase
reverse
a038
Liquid pipe
temp sensor
fault
a039
Ctrl point
sensor disabled
a040
PSU 1/2 power
input failure
a041
Cond pump
fault
a042
Remote
shutdown
Issue 03 (2020-01-10)
Alarm
Impact
Severity
Major
The alarm is
generated, and
the system
shuts down.
Major
The alarm is
generated.
Major
The alarm is
generated.
Major
The alarm is
generated.
Warning
The alarm is
generated.
Major
The humidifier
is shut down.
Critical
The alarm is
generated, and
the system
shuts down.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
Solution
1. The power
1. Check the power supply
supply
frequency is too
2. Replace the SPD
low.
2. The SPD
three-phase test
board is faulty.
The phase
Rectify the phase sequence of
sequence of the
the power supply.
power supply is
incorrect.
1. Cables to the
1. Maintain or replace the
liquid pipe
temp sensor are
2. Check cables to the liquid
not properly
connected.
2. The liquid pipe
temp sensor is
faulty.
All the T/H sensors
Enable the T/H sensors of the
of the control point
control point or change the
are disabled.
control point.
The power input
Check the power input cables
cables of the PSU
of the PSU.
are loose or
damaged.
1. Cables to the
1. Verify pump cable
water pump are
not properly
2. Replace the water pump.
connected.
3. Rectify the liquid level
2. The water
pump is faulty.
4. Remove foreign matter in
3. The water
pump races due
to a liquid level
detection fault.
4. The water
pump is
blocked.
1. The remote
1. Check the status of the
shutdown dry
contact is
triggered.
2. Check the cables to the
2. The cables to
the remote
shutdown dry
contact is
faulty.
frequency.
three-phase test board.
liquid pipe temp sensor.
pipe temp sensor.
connections.
detection fault.
the water pump.
remote shutdown dry
contact.
remote shutdown dry
contact.
155