Exercise caution because the NetCol5000-A is still energized when it is being shut down over
the LCD.
Step 2 Open the front door and disconnect the water pump power cable.
Before removing the water pump, block the water inlet pipe and drainpipe of the water
pump to prevent water overflowing out of the water pan and water pipe.
At the front end of the water pump, block the drain outlet (shown in
water pan using a proper object, such as a cloth based on the actual condition.
At the rear end of the water pump, bend the white drainpipe (shown in
it securely using a proper object, such as a cable tie or rope based on the actual condition.
Figure 6-26 Water pan hole
(1) Water pan hole
Issue 03 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Figure
6-26) of the
Figure
6-27) and tie
212