Parameter
ref. temp
L1/L2
linkage
dehumid
stop ref.
temp
L1/L2
linkage
cooling stop
delay
L1/L2
linkage
fastest temp
rise
L1/L2
linkage
temperature
L1/L2
linkage
humidity
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
teamwork control succeeds, the teamwork topology of the smart cooling product in the group
is displayed, as shown in
Issue 03 (2020-01-10)
Description
L1/L2 linkage.
Reference temperature at
which the smart cooling
product stops
dehumidification in the
dehumidification mode
in L1/L2 linkage.
Duration within which
the device is still cooling
when the cooling stop
condition is met in L1/L2
linkage.
Maximum temperature
rise rate when the
temperature rises rapidly
caused by sudden load
power increase.
Temperature setpoint in
L1/L2 linkage.
Humidity setpoint in
L1/L2 linkage.
2.
Figure
Copyright © Huawei Technologies Co., Ltd.
Configuration
Principle
not recommended to
change the value.
Set this parameter based
on the lowest
temperature allowed
onsite. Normally you are
not recommended to
change the value.
Set this parameter based
on the lowest
temperature allowed
onsite. Normally you are
not recommended to
change the value.
Set this parameter based
on the micro-module size
and maximum load
power. The smaller the
module and the higher
the load power, the
greater the temperature
rise rate is.
Target temperature
controlled in the
micro-module. The
parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
Target humidity
controlled in the
micro-module. The
parameter can only be
modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
4-10.
Table 4-6
describes the note for the screen.
4 ACC Introduction
Default Value
18.0° C
180s
4.0° C/min
24.0° C
45.0%RH