Installation Manual – BTS3606A Cabinet Installation
Airbridge BTS3606&3606A CDMA Base Station
8)
Install the front panel of the air intake box.
Note:
The other end of the GPS clock cable is connected to the "ANT" interface on the BCKM.
5.7 Installing Power Cables
The BTS3606A supports the three-phase 220 V input, two-phase 110 V input, and
single-phase 220 V input. Table 5-8 lists the cables used for different kinds of power
inputs.
Table 5-8 Power cable specifications
Two-phase 110 V
Three-phase 220 V
Single-phase 220 V
5.7.1 Principles of Cabling Power Cables
Note the following principles when cabling power cables:
Place power cables apart from other cables. Never bind them together with other
cables.
Measure the accurate distance from the connecting terminal of the power input to
the outdoor power interface box before laying cables. Be sure to reserve enough
cables, as shown in Figure 5-37.
Name of the
Input
power cable
Live line (L)
Null line (N)
Live line (L)
Null line(N)
Live line (L)
Null line(N)
Huawei Technologies Proprietary
Quantity
2
35 mm
1
35 mm
3
16 mm
1
35 mm
1
25 mm
1
25 mm
5-35
Chapter 5 Installing Cables
Cross-sectional
Color
area
2
2
(41.86 ft
)
Read
2
2
(41.86 ft
)
Black
2
2
(19.14 ft
)
Red
2
2
(41.86 ft
)
Black
2
2
(29.9 ft
)
Red
2
2
(29.9 ft
)
Black