78/84
Display
Description
00000002
More than 32
consecutive
attempts to
communicate
with or initialise
the MMI devices
have failed.
00000010
UNUSED
00000004
UNUSED
00000001
Insufficient time
to complete
power failure
routine.
8.2

Formatted commands and error codes

© Landis+Gyr
If error is persistent
Energy measurement is
compromised.
Communication with
measurement device(s)
has failed and some or
all energy is not
measured.
Energy registers may be
missing up to 60 minutes
worth of energy
consumption and power-
fail data per power-down.
If a formatted command is not properly executed, one of the following
error codes is sent in response to any R1/R2/W1/W2/E2 command:
ER20: If the user does not have read or write permissions to that
section.
ER23: If an unsupported command is sent to the meter.
ER26: If there is an error in reading from or writing to EEPROM.
ER30: If the user has read or write permissions, but command data
is not valid (e.g. the IEC device address must be numeric only: if the
user tries to write 999A0999 in the address, the response will be
ER30).
If none of the above cases are true and there are still problems with
communication, "NAK" (not acknowledged) is sent in response.
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
If error is transitional
Only by power-cycle.
Clear Error Register
F.F.0 on display and
readout by "Reset Error
Register" (W2 C150)
command using
.MAP110 or by power-
cycle.
Error handling
Related
event
log #
N/A
89