Installation and commissioning
5.6.1

Installation mode

D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
4. Connect a load and check the power indicator and energy direction
display on the meter.
The power indicator provides a rough idea of the power applied (for
values, see section 6.1 Customer display). With a smaller load,
particularly close to starting or no load, the meter requires a little time
(up to 10 s) before indicating the relevant value. This also applies to the
display of energy direction.
5. Switch off the load again.
If no load is present, the energy direction arrow disappears and the
power indicator only shows the upper bar.
6. Check the tariff display and switch the control voltage on and off at
the tariff input. The arrow symbol of the tariff display must change.
7. If the meter is operating correctly, screw on the terminal cover.
Otherwise first locate and eliminate the error.
8. Seal the terminal cover with two company seals.
This is an optional feature. During a configurable period of up to 240
minutes, the meter will display all energy registers to three decimal
places irrespective of the configuration. If the meter is configured this
way, every power up occurrence of the meter in the installation mode is
triggered for the defined duration of time. However, it is more common
and also possible to manually enable and disable the installation mode
by formatted command using the .MAP110 meter support tool (see
formatted commands "Enable Test Mode" and "Disable Test Mode").