58/84
6.8

Billing (stored values) (ZMR100xR only)

© Landis+Gyr
Old maximum demand values are added to the cumulative registers
Continual demand register is stored in the Previous MD register
Current MD registers are then cleared
A total of 15 billing (stored values) are available via IEC readout and in
the LCD. Billing periods can be closed/reset automatically by means of a
configured date and time each month or at a specific time on the last
calendar day of the month. Manual closure/reset is also possible by
formatted command and use of the orange MD button (where fitted).
Each billing capture will always contain a date and time stamp and a
billing reset count number. In addition, they may be defined with any
combination of the following parameters (maximum 10):
Energy register channel 1-8, for up to six rates each, plus total
registers
MD register channel 1-4, for up to six rates each, plus total registers
Operating time registers for up to six rates, plus total register
Average power factor
Battery operating time
Terminal cover removal event (special Bulgarian parameter)
Since there are a limited number of segments available in the OBIS
legend, implementation of a 2 second toggle between parts of the OBIS
designation in both auto cycle and manual cycle modes of the displays
for all previous billing parameters, is made (excluding the mandatory
date/time and reset counter parameters). The last completed billing
period is always first in previous billing display list. A worked example is
provided below:
Readout
0.1.0 10 (12-12-01;00:00)
0.1.0 10 (10)
1.8.0 10 (000010.55*kWh)
2.8.0 10 (000002.22*kWh)
15.8.0 10 (000002.16*kvarh)
5.8.0 10 (000002.70*kvarh)
6.8.0 10 (000017.69*kVAh)
7.8.0 10 (000010.55*kWh)
8.8.0 10 (000002.22*kWh)
130.8.0 10 (000002.16*kvarh)
C.8.0 10 (00000033)
C.8.1 10 (00000000)
Example Readout