© Landis+Gyr
CS Interface
Type
Standard
Rated Voltage
Max. Voltage
Transmitter Current – On state
Off State
Receiver Current – On state
Off State
Communication Speed
RS485 Interface (ZMR100xR only)
Type
Standard
Nominal Voltage Range
Binary 1 State
Binary 0 State
Communication Speed
Maximum Number of Nodes
Maximum Length
Insulation
Creepage Distance
Impulse Voltage Withstand
Protocols
Pulse Output r53
Type
Standard
Configurable
Pulse Constant
Supply Voltage (typ.)
Supply Voltage (max.)
Current
Pulse Length
Maximum Line Length
D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
Serial bi-directional
IEC 61107 / DIN 66258
24V DC
30V DC
Min.11 mA
Typ. 20 mA
Max. 30 mA
Max. 2.5 mA
Min. 9 mA
Typ. 20 mA
Max. 30 mA
3 mA Max.
300 to 4800 Baud
Half-duplex
ANSI TIA/EIA-485-A and ISO
8482:1993
-7 V to +12 V DC
Difference voltage > 0.2 V
Difference voltage < -0.2 V
300 to 9600 Baud
31
1000 m cable (daisy chain)
4 kV AC/50 Hz, 1 min
6.2 mm
6 kV peak 1.2/50 μs
IEC62056-21 C
S0 Interface (or data stream)
IEC 62053-31
Imp/Wh or imp/VArh
Configurable (1 – 1000)
24 V
50 V
10 mA DC
Configurable (10 ms – 1000 ms)
1000 m
Introduction