No Power Read (Optional Fitting); Tou (Time-Of-Use) Tables (Zmr100Xr Only) - Landis+Gyr E230 User Manual

Residential electricity meter
Table of Contents

Advertisement

Operation
6.5

No power read (optional fitting)

6.6

ToU (Time-of-Use) tables (ZMR100xR only)

D000044352 en g – E230 Residential Electricity Meter – ZxR100xC/ZMR100xR – User Manual
Missing voltage persistence time
Voltage without current persistence time
Under voltage persistence time
Current threshold for voltage without current
Over voltage persistence time
Phase reversal persistence time
Under voltage threshold voltage
KVA threshold for PF monitor
Over voltage threshold voltage
Threshold for PF monitor
Over current persistence time
Voltage imbalance persistence time
Over current threshold current
Lower power factor persistence time
Current balance persistence time
Power On/Off persistence time
Magnet sensor persistence time
Voltage unbalance threshold (V
Current imbalance threshold (I
Threshold for demand monitor Ch1
Threshold for demand monitor Ch2
Threshold for demand monitor Ch3
Threshold for demand monitor Ch4
The No Power Read (NPR) feature allows readings to be taken from the
meter for data collection purposes either via the optical port or from the
LCD display, when there is no mains supply. This function is activated
by pressing and holding the display cycle button or by using the front
panel optical port.
The battery circuitry locks on after about 2 or 3 seconds and provides
about 60 seconds of power in which to read the meter or perform a flag
download. In No Power Read mode, the display sign-on is removed to
conserve power. After this, the display uses the NPR default display and
NPR display cycle. Some functions of the meter are disabled in this
mode (e.g. LEDs and Relays).
After using the battery, a repeat operation cannot be performed for
approximately 60 seconds. To prolong battery life, the number of times
NPR can be activated is restricted to 2 per month.
The E230 ZMR100xR's ToU functionality provides a maximum of 16
output signals to switch:
Energy
Demand tariffs
Control loads
)
max
)
max
53/84
© Landis+Gyr