Maintenance

7.1

Meter testing

7.1.1

Test mode

© Landis+Gyr
This section describes the necessary maintenance work.
Meter tests should be performed at periodic intervals according to the valid
national regulations (either on all meters or on specific random samples). In
principle, the meters should be uninstalled for this purpose according to the
instructions in section 4.6 "Uninstallation" and replaced by a substitute
meter. The meter test can also be performed on the spot in certain
circumstances.
The test mode permits increasing the resolution of the energy registers by 1
to 5 digits. This allows the energy supply company to carry out the so called
measuring unit test in a reasonably short time.
In test mode, the same registers shown as a rolling list in the operating
display are always displayed, but with high resolution and not rolling.
The energy registers comprise a total of 12 digits. A maximum of 8 digits,
however, is shown on the display. The effective number of digits shown and
the number of decimal places are determined by the parameterisation. For
the test mode more decimal places are normally parameterised (maximum
5) to permit a quicker test of the transmission to the energy registers.
Figure 79. Display changeover normal mode – test mode
Changeover from normal to test mode and back is made by formatted
commands (see section 5.8 "Input of formatted commands") or manually in
the service menu.
In test mode, the optical test output for active energy can also provide
reactive energy pulses depending on the parameterisation. Reactive
energy pulses are supplied to this test output if the register shown on the
display represents a reactive energy register. Active energy pulses are
supplied for all other measured values shown as in normal operating mode.
Formatted commands can also be used to define whether the optical test
output for active energy in test mode should supply active or reactive
energy pulses, independent of the type of register shown on the display.
This permits changeover without manual intervention.
D000062026 en a – E650 Series 4 – ZMD400AT/CT, ZFD400AT/CT – User Manual