Diagnostics and troubleshooting
11.2 Diagnostics
11.2.4.24
Diagnostic value '28.SSUP - Slow step zone up' / '29.SSDN - Slow step zone down'
Display range:
Purpose:
Factory setting:
See also
Mode of operation (Page 30)
Optimization of controller data (Page 101)
11.2.4.25
Diagnostic value '30.TEMP - Current temperature'
Display range:
Purpose:
11.2.4.26
Diagnostic value '31.TMIN - Minimum temperature' / '32.TMAX - Maximum temperature'
Display range:
Purpose:
224
0.1 ... 100.0
The slow step zone is the zone of the closed-loop controller in which
control signals are issued in a pulsed manner. Display is in percent.
The impulse length is thus proportional to the control deviation. If
the control deviation is beyond the slow step zone, the valves are
controlled using permanent contact.
This parameter can be set for special applications.
10.0
°C: -50 ... 100
°F: -58 ... 212
Current temperature in the positioner enclosure. The sensor is
present on the basic electronics. In order to switch over the temper‐
ature display between °C and °F, press the
°C: -50 ... 100
°F: -58 ... 212
The minimum and maximum temperatures within the enclosure are
constantly determined and saved as with a min/max pointer. This
value can only be reset in the factory.
In order to switch over the temperature display between °C and °F,
press the
button.
button.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE