Siemens SIPART PS2 Series Operating Instructions Manual page 284

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

External position detection
B.2 Non-Contacting Sensor
Additional modules
Linearity (after corrections made by
positioner)
Hysteresis
Temperature influence (range: rota‐
tion angle 120° or stroke 14 mm)
Climate class
● Storage
● Transport
Vibration resistance
● Harmonic oscillations
(sine) according to IEC 60068-2-6
● Bumping according to IEC
60068-2-29
Torque for cable gland nut made of
Torque of hexagon socket-head
screw M6x12 (shaft end or mounting
bracket)
Torque of hexagon socket head screw
M6x25 (mounting console or mount‐
ing plate)
Torque of hexagon socket head screw
M3x12 (clamping ring)
Degree of protection
For connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
C
= 110 nF + 110 nF per meter of connecting cable
1)
i
L
= 270 µH + 6.53 µH per meter of connecting cable
2)
i
284
Without Ex protection
≤ 0.1 %/10 K (≤ 0.1 %/18 °F) for -20 to +90 °C (-4 to +194 °F)
≤ 0.2%/10 K (≤ 0.2%/18 °F) for -40 to -20 °C (-40 to -4 °F)
1K5, but -40 to +90 °C (-40 to +194 °F)
2K4, but -40 to +90 °C (-40 to +194 °F)
3.5 mm (0.14"), 2 to 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axis
300 m/s
Plastic
2.5 Nm (1.8 ft lb)
-
-
-
With Ex protection
Ex "ia"
± 1 %
± 0.2 %
According to IEC/EN 60721-3
(984 ft/s
), 6 ms, 4000 shocks/axis
2
2
Metal
4.2 Nm (3.1 ft lb)
4 Nm (3 ft lb)
4 Nm (3 ft lb)
1 Nm (0.7 ft lb)
IP68 / type 4X
U
= 5 V
i
I
= 160 mA
i
P
= 120 mW
i
C
=
1)
i
L
=
2)
i
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
With explosion protection
Ex "ic", "ec"
Stainless steel
4.2 Nm (3.1 ft lb)
U
= 5 V
i
C
=
1)
i
L
=
2)
i

Hide quick links: