Initialization Of Part-Turn Actuators; Initializing Linear Actuators With A Stroke Range Up To 14 Mm (0.55 Inch); Initializing Linear Actuators With A Stroke Range > 14 Mm (0.55 Inch); Technical Specifications Ncs - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

B.2.4.2

Initialization of part-turn actuators

Procedure
1. For part-turn actuators operating in standard control direction, set parameter "1.YFCT" to
"ncSt", or to "-ncSt" in case of inverse control direction.
2. Launch initialization as usual with "INITA".
B.2.4.3

Initializing linear actuators with a stroke range up to 14 mm (0.55 inch)

Requirements
1. Set the "1.YFCT" parameter of the positioner to "ncSL" or - with inverse control direction -
to "-ncSL".
2. Launch initialization as usual with "INITA".
B.2.4.4
Initializing linear actuators with a stroke range > 14 mm (0.55 inch)
Note
Parameter values "ncSLL" and "-ncLL" are only available for devices of the 6DR5... series and
only with the firmware version > C4. Set the value to 90° on devices of the 6DR5... series with
firmware version < C5 (YAGL). This setting is also necessary for devices of the 6DR4... series.
Resultant non-linearity can be corrected by means of the programmable characteristic by
setting the parameter value from "SFCT" to "FrEE" and adapting the interpolation points.
Requirements
1. Set the "1.YFCT" parameter of the positioner to "ncSLL" or - with inverse control direction
- to "-ncLL".
2. Launch initialization as usual with "INITA".
B.2.5

Technical specifications NCS

Additional modules
Travel range
● Linear actuator 6DR4004-6/8N.20
● Linear actuator 6DR4004-6/8N.30
● Part-turn actuator
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
Without Ex protection
10 to 130 mm (0.39 to 5.12"); up to 200 mm (7.87") on request
B.2 Non-Contacting Sensor
With Ex protection
Ex "ia"
3 to 14 mm (0.12 to 0.55")
30 to 100°
External position detection
With explosion protection
Ex "ic", "ec"
283