5.2.3.5
Analog Input Module (AIM) 6DR4004-6F / -8F
Procedure
1. Connect the external position detection as follows.
①
Connection of terminal Vcc is only needed for 6DR4004-2ES, -3ES and -4ES.
2. If potentiometers or external signal sources are used, configure the switch blocks in
accordance with the following table:
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
1
Measuring range
6DR4004-.N/P/R (NCS)
6DR4004-1ES/-2ES/-3ES/-4E
S
10 ... 20 kΩ
5 kΩ
3 kΩ
20 mA
10 V
Switch block 1
S1-1
S1-2
S2-1
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
Connection
5.2 Electrical wiring
Switch block 2
S2-2
S2-3
S2-4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
87