Siemens SIPART PS2 Series Operating Instructions Manual page 72

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Installing/mounting
4.5 Installing option modules
Procedure
Figure 4-21
1. Open the positioner as described in Opening the standard and intrinsically safe version
(Page 52).
2. Remove the ribbon cable from the basic electronics.
3. Loosen the two fixing screws of the basic electronics
4. Remove the basic electronics.
5. Loosen the screw
6. Insert the connector of the ribbon cable (A) into the slot as shown below.
Note: There is no space for the ribbon cable (A) in earlier versions of the positioner. Here
you fasten the ribbon cable with the supplied cable tie at the container.
7. Secure the Analog Input Module (AIM) using the screw
8. Place the basic electronics
9. Screw in the two fixing screws of the basic electronics
10.Tighten the screws.
72
Terminals of the Analog Input Module (AIM)
Yellow wheel for locking the position detection
Positioner
Ribbon cable connector of fitted potentiometer
or ribbon cable connector of Analog Input Mod‐
ule (AIM)
Installation of Analog Input Module (AIM)
in the connection area of the positioner.
onto the four holders of the adapter.
Operating Instructions, 11/2019, A5E00074631-AE
Basic electronics
Screw
Analog Input Module (AIM)
6DR4004-6F/-8F
.
.
.
SIPART PS2 with 4 to 20 mA/HART

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents