Siemens SIPART PS2 Series Operating Instructions Manual page 157

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Note
If extended diagnostics is activated using parameter "'52.XDIAG' Activating for extended
diagnostics (Page 162)" with setting "On3", then the alarms are not output through the Digital
I/O Module (DIO). Alarm A1 is output with setting "On2". However, notification via the
communication interface is possible at any time.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
Direction of action and hysteresis
Parameter assignment
8.4 Description of parameters
Digital I/O Module
(DIO)
Examples
A1
A1 = 48
AFCT = MIN / MAX
A2 = 52
Way =45
Active
Way =50
Way =55
A1 = 48
AFCT = -MIN / -MAX
A2 = 52
Way =45
Way =50
Active
Way =55
Active
A1 = 52
AFCT = MIN / MAX
A2 = 48
Way =45
Active
Way =50
Active
Way =55
A1 = 52
AFCT = -MIN / -MAX
A2 = 48
Way =45
Way =50
Way =55
Active
A2
Active
Active
Active
Active
Active
Active
157