Electrical Connection Of 19" Slide-In Module 4 To 20 Ma - Siemens SIPART PS2 Series Operating Instructions Manual

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Positioner with remote control electronics
F.2 19" slide-in module
Figure F-3
Grounding concept of 19" slide-in module 4 to 20 mA version
Notes on the individual connection points:
F.2.2.2

Electrical connection of 19" slide-in module 4 to 20 mA

Requirement
You have read sections Connection (Page 75) and Grounding concept of 19" slide-in module
4 to 20 mA (Page 312).
314
The cable shield is not connected to the positioner 6DR5910.
The positioner 6DR5910 is connected via the mechanical assembly to Ground 2 ,
see Installing/mounting (Page 37). Section Basic safety instructions (Page 75) de‐
scribes how to ground the enclosure.
Each field distributor is grounded. The cable shields in the field distributor are not
grounded. The cable shields are interconnected.
The cable shields on the 19" slide-in module are connected to the field distributor.
The 19" slide-in module is connected to Ground 1.
The cable shields on the control system are not connected to ground.
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE