Commissioning

7.11 Commissioning part-turn actuators

7.11
Commissioning part-turn actuators
7.11.1

Preparing part-turn actuators for commissioning

Note
Setting of the adjustment angle
The usual adjustment angle for part-turn actuators is 90°.
● Set the transmission ratio selector in the positioner to 90°.
Condition
The following conditions must be fulfilled before activating the initialization:
1. You have installed the positioner for the part-turn actuators using the suitable mounting kit.
2. You have connected the actuator and the positioner to the pneumatic lines.
3. Supplying the positioner with the supply pressure PZ.
4. The positioner has been connected to a suitable power supply.
Setting the actuator
1. The positioner is in the "P manual mode". The current potentiometer voltage P in percent is
shown on the upper line in the display. "NOINI" blinks in the lower line of the display.
Examples of corresponding displays are given below:
2. Check whether the mechanical unit can be moved freely in the entire travel range. Move the
drive to the respective end position for this purpose using the
Note
End position
By simultaneously pressing the
3. After checking, move the actuator to a central position. This accelerates the initialization
process.
124
and
buttons, you reach the end position faster.
Operating Instructions, 11/2019, A5E00074631-AE
or
button.
SIPART PS2 with 4 to 20 mA/HART

Hide quick links:

Advertisement

Table of Contents
loading