Diagnosis; Diagnostic Display - Siemens SIPART PS2 6DR5020 Series Manual

Electropneumatic positioner for linear and rotary actuators
Table of Contents

Advertisement

Operation
4.5

Diagnosis

4.5.1 Diagnostic display

No.
Abbrevia-
Meaning
tion
1
STRKS
Number of strokes (Strokes)
2
CHDIR
Changes of direction (Changes of Direction)
3
Fault counter (Counter )
CNT
4
A1CNT
Alarm counter 1 (Alarm 1 Counter)
5
A2CNT
Alarm counter 2 (Alarm 2 Counter)
6
HOURS
Operating hours (Hours)
7
WAY
Determined actuating path (Way)
8
TUP
Travel time up (Travel Time Up)
9
TDOWN
Travel time down (Travel Time Down)
10
LEAK
Leakage (Leakage)
11
P0
Potentiometer value below stop (0%)
12
P100
Potentiometer value bottom stop (100%)
13
IMPUP
Impulse length up (Impulse Length Up)
14
IMPDN
Impulse length down (Impulse Length Down)
15
DBUP
Dead zone up (Dead Band Up)
16
DBDN
Dead zone down (Dead Band Down)
17
SSUP
Short step zone up (Short Step Zone Up)
18
SSDN
Short step zone down (Short Step Zone Down)
19
TEMP
Current temperature
20
TMIN
Minimum temperature ("drag pointer")
21
TMAX
Maximum temperature ("drag pointer")
22
T1
Number of operating hours in Temperature range 1
23
T2
Number of operating hours in Temperature range 2
24
T3
Number of operating hours in Temperature range 3
25
T4
Number of operating hours in Temperature range 4
26
T5
Number of operating hours in Temperature range 5
27
T6
Number of operating hours in Temperature range 6
90
You go to the diagnostic display from automatic or manual operation by
simultaneously pressing all three keys for at least two seconds.
Table 3-1, page 91 shows an overview of the displayable values. In the
third column the corresponding English term from which the abbrevia-
tion is derived is shown next to the German meaning unless this is self
explanatory.
The diagnostic display has a similar structure to in the "Configuration"
operating mode. the top line shows the value of the diagnostic variable,
the bottom line the number and abbreviation of the displayed variable.
The respective next diagnostic value can be selected with the operation
mode key
. By pressing and holding the operation mode key and
additionally pressing the decrement key
stic values in reverse order.
Certain values can be set to zero by pressing the increment key
at least 5 seconds. This is noted in the last column in the table.
Some diagnostic values may be greater than 99999. In this case the
display switches to exponential display. Example: the value 1234567 is
displayed as 1.23E6.
you can select the diagno-
Displayable
Unit
values
0 to 4.29E9
- -
0 to 4.29E9
- -
0 to 4.29E9
- -
0 to 4.29E9
- -
0 to 4.29E9
0 to 4.29E9
Hours
0 to 130
mm or _
0 to 1000
s
0 to 1000
s
0.0 to 100.0
%
0.0 to 100.0
%
0.0 to 100.0
%
2 to 100
ms
2 to 100
ms
0.1 to 100.0
%
0.1 to 100.0
%
0.1 to 100.0
%
0.1 to 100.0
%
- -40 to 85
_C
- -40 to 85
_C
- -40 to 85
_C
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
SIPART PS2 Manual