Technical data
12.10 Option modules
12.10.5

Analog Input Module (AIM) 6DR4004-6F / -8F

The Analog Input Module (AIM) 6DR4004-6F and -8F is required to connect a Non-Contacting Sensor (NCS) or Position
For devices without explosion protection, other types of potentiometers with resistance values between 3 and 20 KΩ can be
R-potentiometer
● Peak values when supplied by other
basic devices (6DR50/1/2/3/9)
● Maximum values when powered by the
base unit with PA (6DR55) or FF com‐
munication (6DR56)
Signal 20 mA
● Rated signal range
● Internal load R
B
● Static destruction limit
Signal 10 V
● Rated signal range
● Internal resistance R
i
● Static destruction limit
Supply and signal power circuits
12.10.6

Internal NCS module 6DR4004-5L / 6DR4004-5LE

Additional modules
Linearity (after corrections made by
positioner)
Hysteresis
For connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
254
Without explosion
protection
6DR4004-8F
Transmitter 6DR4004-1ES to -4ES.
connected.
U
= 5 V
max
U
= 5 V
max
0 ... 20 mA
200 Ω
40 mA
0 ... 10 V
25 kΩ
20 V
Galvanically connected with the basic device
Without explosion protec‐
tion
6DR4004-5L
-
-
-
With explosion protection
Ex "ia", "db ia", "ic"
6DR4004-6F
U
≤ 5 V
o
I
≤ 100 mA
o
P
≤ 33 mW
o
C
≤ 1 μF
o
L
≤ 1 mH
o
U
≤ 5 V
o
I
≤ 75 mA static
o
I
≤ 160 mA transient
o
P
≤ 120 mW
o
C
≤ 1 μF
o
L
≤ 1 mH
o
With explosion protection
Ex "ia", "db ia"
6DR4004-5LE
± 1 %
± 0.2 %
U
≤ 5 V
i
I
≤ 160 mA
i
P
≤ 120 mW
i
C
= 110 nF + 110 nF per meter of connecting cable
i
L
= 270 µH + 6.53 µH per meter of connecting cable
i
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
With explosion protection
Ex "ec", "tb"
6DR4004-6F
U
= 5 V
max
U
= 5 V
max
-
-
-
-
-
-
With explosion protection
Ex "ic", "ec", "tb"
6DR4004-5LE
U
≤ 5 V
i