Alarm, error, and system messages
10.2 Diagnostics
10.2.4.21

Diagnostic value '25.PAUTP - Pulse interval'

Display range:
Purpose:
Factory setting:
See also
Mode of operation (Page 28)
10.2.4.22

Diagnostic value '26.DBUP - Deadband UP' / '27.DBDN - Deadband DOWN'

Display range:
Purpose 1
10.2.4.23

Diagnostic value '28.SSUP - Slow step zone UP' / '29.SSDN - Slow step zone DOWN'

Display range:
Purpose:
Factory setting:
See also
Mode of operation (Page 28)
Optimization of controller data (Page 110)
220
2 ... 320
This value is not changed during an initialization process. Display
in ms.
For applications with high stiction (slipstick), adjusting this parame-
ter improves the control quality.
This parameter can be set for special applications.
28
0.1 ... 10.0
In this parameter, you can read the deadbands of the controller in
the 'Up' and 'Down' directions. Display in percent. The values cor-
respond either to the manually configured value of the '34.DEBA'
Deadband of closed-loop controller (Page 163) parameter or to the
value automatically adapted by the device if 'DEBA' was set to 'Au-
to'.
0.1 ... 100.0
The slow step zone is the zone of the closed-loop controller in
which control signals are issued in a pulsed manner. Display is in
percent. The impulse length is thus proportional to the control de-
viation. If the control deviation is beyond the slow step zone, the
valves are controlled using permanent contact.
This parameter can be set for special applications.
10.0
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB