U4.PZ_FR - Error response on undershoot of the supply pressure
Possible settings:
Purpose:
Factory setting:
8.5

Overview of the assignment of the HART variables

Dynamic variables for device revision 6, as of firmware 5.01.xx HART 7
For positioners with HART communication, the variables PV, SV, TV and QV are assigned as
follows:
Variable
HART Primary Variable (PV)
HART Secondary Variable (SV)
HART Tertiary Variable (TV)
HART Quaternary Variable (QV)
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
8.5 Overview of the assignment of the HART variables
cont / HOLd
Defines the behavior of the device when the limit value of the supply
pressure (U2.PZLIM) is undershot.
Cont = Chamber pressure is controlled via supply pressure PZ.
HOLd = Chamber pressure is maintained, corresponds to the re‐
sponse for Fail in Place.
cont
Meaning
Primary variable
1st secondary variable
2nd secondary variable
3rd secondary variable
Parameter assignment
Physical variable
W (setpoint) in %
X (actual value) in %
Xd (control deviation) in %
t (temperature) in °C