Siemens SIPART PS2 Series Operating Instructions Manual page 141

Electropneumatic positioners with 4 to 20 ma/hart
Hide thumbs Also See for SIPART PS2 Series:
Table of Contents

Advertisement

Overview parameter d
Parameter
Function
d. STIC
Monitoring of stiction (slipstick) with the following parameters:
d1.LIMIT
Limit
d2.FACT1
Factor 1
d3.FACT2
Factor 2
d4.FACT3
Factor 3
Overview parameter E
Parameter
Function
E. DEBA
Monitoring of deadband with the following parameters:
E1.LEVL3 *) Threshold
*) The values are monitored in the range of '0.1' to '2.9'. Values between '3.0' and '10.0' are not
monitored.
Overview parameter F
Parameter
Function
F. ZERO
Monitoring of lower endstop with the following parameters:
F1.LEVL1
Threshold 1
F2.LEVL2
Threshold 2
F3.LEVL3
Threshold 3
Overview parameter G
Parameter
Function
G. OPEN
Monitoring of upper endstop with the following parameters:
G1.LEVL1
Threshold 1
G2.LEVL2
Threshold 2
G3.LEVL3
Threshold 3
Overview parameter H
Parameter
Function
H. TMIN
Monitoring of lower limit temperature with the following parameters:
H1.TUNIT
Temperature unit
H2.LEVL1
Threshold 1
H3.LEVL2
Threshold 2
H4.LEVL3
Threshold 3
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E00074631-AE
8.3 Tabular overview of the parameters
Parameter values
0.1 ... 1.0 ... 100.0
0.1 ... 2.0 ... 100.0
0.1 ... 5.0 ... 100.0
0.1 ... 10.0 ... 100.0
Parameter values
0.1 ... 2.0 ... 10.0
Parameter values
0.1 ... 1.0 ... 10.0
0.1 ... 2.0 ... 10.0
0.1 ... 4.0 ... 10.0
Parameter values
0.1 ... 1.0 ... 10.0
0.1 ... 2.0 ... 10.0
0.1 ... 4.0 ... 10.0
Parameter values
°C
°F
-40 ... -25 ... 90
-40 ... 194
-40 ... -30 ... 90
-40 ... 194
-40 ... 90
-40 ... 194
Parameter assignment
Unit
%
Unit
%
Unit
%
Unit
%
Unit
°C/°F
141