3.1.4.2

Terminal Module TM31

Table 3- 44
Meanings of the LEDs on the Terminal Module TM31
LED
Color
READY
-
Green
Orange
Red
Green/red
Green/
orange or
Red/
orange
3.1.4.3

Terminal Module TM120

Table 3- 45
Meaning of the LEDs on the Terminal Module TM120
LED
Color
Status
-
Off
Green
Continuous
light
Orange
Continuous
light
READY
Red
Continuous
light
Green/
Flashing
Red
light
0.5 Hz
Flashing
light
2 Hz
Green/
orange or
Flashing
red/
light
orange
2 Hz
Commissioning Manual
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Status
OFF
Electronics power supply is missing or outside the
permissible tolerance range.
Continuous light The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Continuous light DRIVE-CLiQ communication is being established.
Continuous light At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
0.5 Hz flashing
Firmware is being downloaded.
light
2 Hz flashing
Firmware download is complete. Wait for POWER ON
light
Flashing light
Component recognition via LED is activated (p0154).
Note:
Both options depend on the LED status when component
recognition is activated via p0154 = 1.
Description, cause
Electronics power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component. Note:
The LED is activated regardless of whether the corresponding
messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON
Detection of the components via LED is activated (p0154).
Note:
Both options depend on the LED status when module
recognition is activated via p0154 = 1.
Description, cause
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Remedy and
acknowledge fault
Carry out a
POWER ON
Remedy
Check power supply
-
-
Remedy and
acknowledge fault
-
Carry out a POWER
ON
-