Diagnostics
3.1 Diagnostics via LEDs
3.1.2.4

Smart Line Modules booksize 16 kW to 55 kW

Table 3- 18
Meaning of the LEDs at the Smart Line Modules ≥ 16 kW
State
Ready
DC link
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
Green / red
flashing light
0.5 Hz
Green / red
flashing light
2 Hz
Green /
orange
or
Red / orange
flashing light
Risk of electric shock as a result of the high DC link voltage
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
link" LED.
Note the warning information on the component!
252
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding
messages being reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
WARNING
Remedy
Check the line voltage
Remedy and acknowledge
fault
Carry out a POWER ON
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3