Commissioning With Starter (Example) - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Commissioning
2.5 Commissioning U/f vector control booksize format for the first time
2.5.4

Commissioning with STARTER (example)

The table below describes the steps for commissioning the example using the STARTER
commissioning tool.
Table 2- 6
Commissioning sequence (example)
What?
1.
Creating a new
project
2.
Automatic
configuration
3.
Configure the
infeed
Note:
When the factory setting is p7826 = 1, the firmware is automatically updated to the status on the memory card when a
configured DRIVE-CLiQ component is first booted. This may take several minutes and is indicated by the READY-LED on
the corresponding components flashing green/red and the Control Unit flashing orange (0.5 Hz). Once all updates have
been completed, the READY-LED on the Control Unit flashes orange at 2 Hz and the corresponding READY-LED on the
components flashes green/red at 2 Hz. For the firmware to be activated, a POWER ON must be carried out for the
components.
For infeed units connected to the drive unit, which during the automatic configuration do not communicate with the Control
Unit via DRIVE-CLiQ, you must manually configure and transfer into the drive topology. These devices can only be
inserted in the offline mode.
102
How?
1. Call the menu "Project > New...".
2. Assign a new name in the "New project" dialog.
3. Click "OK".
1. Call the menu "Project > Connect to selected target devices".
As there is still no device available in the project, STARTER
offers the option of searching for accessible nodes.
2. Click on "Yes".
3. Activate the drive unit reached by clicking on the check box.
4. Click on "Apply".
The drive unit is transferred into the project window.
5. Call the menu again "Project" > "Connect to selected target
devices".
You are now connected online with the drive unit.
6. Double-click on "Automatic configuration". Click on
"Configure".
7. During automatic commissioning, the wizard will offer you the
option of selecting the drive object type. As default
assignment, select all of the "Vector" components.
8. Click on "Create".
9. After the automatic configuration has been completed, you
have the option of going OFFLINE or remaining ONLINE.
Select "Go OFFLINE".
1. Double-click in the project tree on "Infeeds".
2. Double-click on the infeed that has been created.
3. Click on the yellow button "Wizard...".
4. To check the automatic settings and to enter additional data,
such as equipment codes etc. continue with Point 3.2.
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Comment
-
-
-
Commissioning Manual

Advertisement

Table of Contents
loading

Table of Contents