Sequence: Establishing the online mode with PROFINET
1. Setting the IP address in Windows XP
2. Settings in the STARTER commissioning tool
3. Select online operation in the STARTER commissioning tool.
Setting the IP address in Windows XP
1. On the desktop, click on the symbol "Network Environment" and click the right mouse
2. Double-click the appropriate network card and then click "Properties".
3. Select the Internet Protocol (TCP/IP) and click the "Properties" button.
4. Then enter IPs for the "IP address" and the "Subnet mask".
Setting the interface in the STARTER commissioning tool
In the STARTER commissioning tool, you set communication via PROFINET as follows:
1. Call the menu "Tools > Set PG/PC interface ...".
Commissioning Manual
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Assign the programming device (PG/PC) a fixed, free IP address. In our example, we
selected 169.254.11.1, based on the factory setting of the integrated Ethernet interface
X127 (169.254.11.22). Set the subnet mask to 255.255.0.0.
button to open the "Properties" shortcut menu.
Figure 2-11
Internet Protocol (TCP/IP) properties
Commissioning
2.2 STARTER commissioning tool
75