Diagnostics
3.1 Diagnostics via LEDs
Table 3- 6
Orange
Control Unit 320-2 PN in operation
Table 3- 7
Control Unit CU320-2 PN – Description of the LEDs after booting
LED
Color
RDY
–
(READY)
Green
Red
Red/
green
Orange
Green/
orange
or
red/
orange
PN
–
PROFIdrive
cyclic
operation
Green
242
Firmware
LED
RDY
PN
Off
Alternating
Status
Description, cause
OFF
Electronics power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Flashing
Commissioning/reset
light
0.5 Hz
Flashing
Writing to the memory card
light
2 Hz
Flashing
General error
light
2 Hz
Flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz
Flashing
Updating the firmware of the DRIVE-CLiQ
light
components
0.5 Hz
Flashing
DRIVE-CLiQ component firmware update
light
complete. Wait for POWER ON for the
2 Hz
components in question.
Flashing
Component detection via LED is activated
light
(p0124[0]).
2 Hz
Note:
Both options depend on the LED status when
component recognition is activated via
p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Note:
PROFIdrive is ready for communication when the
Control Unit is ready (see LED RDY).
Continuous
Cyclic communication is taking place.
light
Status
OPT
Off
Initializing
Running
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Comment
–
See the table below
Remedy
Check power supply
–
–
–
Check parameterization /
configuration
Obtain licenses
–
Turn POWER ON for the
components in question
–
–
–
Commissioning Manual