Diagnostics
3.1 Diagnostics via LEDs
3.1.2.8
Motor Module booksize compact format
Table 3- 22
Meaning of the LEDs on the Motor Module booksize compact
State
RDY
DC LINK
Off
Off
Green
–
Orange
Red
Orange
Orange
Red
–
Green/red
–
(0.5 Hz)
Green/red
–
(2 Hz)
Green/
–
orange
or
red/orange
Risk of electric shock as a result of the high DC link voltage
Hazardous DC link voltages may be present at any time regardless of the state of the LED
"DC LINK".
Note the warning information on the component!
256
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding
messages being reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
WARNING
Remedy
–
–
–
Check the line voltage
–
Remedy and acknowledge
fault
–
Carry out a POWER ON
–
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3