Commissioning
2.7 First commissioning vector control AC drive blocksize format
Procedure
14.
p1036[0] =
r0019.0014
(DO 1)
15.
p1070[0] =
r1050 (DO 63)
16.
"FN", then press "P". The display indicates 41, press "O", the display jumps to 31.
17.
Start the motor data identification with "I". The drive switches off again after approx. 5 sec., the display goes back
to 41.
18.
After pressing "O", 31 is displayed again. The drive is now ready. The drive is switched on by pressing "I", the
motor accelerates by pressing the "↑" key.
19.
Save all
parameters
* These parameters offer more setting options than the ones described here. For further setting options see
SINAMICS S120/S150 List Manual
[CDS] Parameter depends on command data sets (CDS). Data set 0 is preset.
[DDS] Parameter depends on drive data sets (DDS). Data set 0 is preset.
[MDS] Parameter depends on motor data sets (MDS). Data set 0 is preset.
BI binector input
BO binector output
CI connector input
CO connector output
126
BI: Motor potentiometer setpoint lower [CDS]
Sets the signal source to reduce the setpoint for the motorized potentiometer
Interconnection with r0019.014 of the drive object Control Unit (DO 1)
Effect: Signal, motorized potentiometer lower setpoint from BOP
CI: Main setpoint [CDS]
Sets the signal source for speed setpoint 1 of the speed controller.
Interconnection with r1050.000 to the separate drive object (DO 63)
Effect: Motorized potentiometer supplies the speed setpoint
Press the P key for approx. 5 sec until the display flashes.
Description
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Factory
setting
0
0
Commissioning Manual