Commissioning
2.16 Temperature sensors for SINAMICS components
Faults and alarms
F07011 drive: Motor overtemperature
KTY sensor:
The motor temperature has exceeded the fault threshold (p0605) or the timer stage (p0606)
after the alarm threshold was exceeded (p0604) has expired.
This results in the reaction parameterized in p0610.
PTC sensor + bimetallic switch:
The response threshold of 1650 Ohm was exceeded and the timer stage (p0606) has
expired.
This results in the reaction parameterized in p0610.
If an SME Module is used (p0601 = 10), parameter r949 displays the number of the sensor
channel that has triggered the message.
A07015 drive: Motor temperature sensor alarm
An error was detected when evaluating the temperature sensor set in p0600 and p0601.
When the fault occurs, the time in p0607 is started. If the fault is still present after this time
has expired, fault F07016 is output – however, not until at least 50 ms after alarm A07015.
If an SME Module is used (p0601 = 10), parameter r2124 displays the number of the sensor
channel that has triggered the message.
F07016 drive: Motor temperature sensor fault
An error was detected when evaluating the temperature sensor set in p0600 and p0601.
If alarm A07015 is present, the time in p0607 is started. If the fault is still present after this
time has expired, fault F07016 is output – however, not until at least 50 ms after alarm
A07015.
If an SME Module is used (p0601 = 10), parameter r949 displays the number of the sensor
channel that has triggered the message.