2. Align the system unit on to the rails and push the system unit back into the rack until both release
latches lock into position. See Figure 223.
Figure 223. Placing the system into the operating position
3. Replace the screws on either side of the system that secure the system to the rack.
Fixed rails
Use this procedure when your system is installed using fixed rails.
Before you begin
CAUTION:
This system requires two people to replace the system into the rack. Do not begin this procedure
unless physical assistance is available to replace the system into the rack.
Note: When you place the system into the operating position, you must ensure that all stability plates are
firmly installed to prevent the rack from toppling. Ensure that only one system unit is replaced at a time.
Procedure
1. Position one person on the left side of the system and one person on the right side of the system.
2. Lift the system.
3. Tilt the system into position over the fixed rack rails.
4. Carefully lower the system until the rear of the system rests on the rails.
5. While one person is supporting the weight of the system, have the second person move to the front of
the system and push the system all the way into the rack.
6. Using your labels, reconnect the cables at the rear of the system unit.
7. For a water-cooled system, connect the water hoses at the rear of the rack to the manifold, as shown
in Figure 224 on page 209. Ensure that you plug the male hose into the female manifold plug, and
plug the female hose into the male manifold plug.
208
Power Systems: Servicing the IBM Power System S822LC (8335-GTB)