Figure 31. Replacing the holder back onto the carrier
The cold plate is secured to the carrier. Repeat step 6 on page 22 for each cold plate.
What to do next
Next, do this procedure: "Replacing the cold plates in the 8335-GTB system."

Replacing the cold plates in the 8335-GTB system

Learn how to replace the cold plates in the water-cooled IBM Power System S822LC (8335-GTB) system.
Before you begin
Ensure that you have enough TIMs for the GPUs and processors. Check the FRU kit. The GPU TIM part
number is: 00E5133. The processor TIM part number is 45D7426.
Procedure
1. Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
2. Ensure that each GPU clip is open as shown in Figure 32 on page 25.
24
Power Systems: Servicing the IBM Power System S822LC (8335-GTB)